Actionair
THERMSHIELD FDC
THERMSHIELD FDC is a circular single-blade fire damper, CE-marked with an EIS classification, with mechanical or automatic operation. It restores fire compartmentation in ventilation systems with circular ducts, preventing the spread of fire and smoke. It covers diameters from 100 to 800 mm and is available with a manual or electric actuation mechanism.
Download Technical Datasheet (PDF)Technical Specifications
CategoryPassive Fire Protection
BrandActionair
Control compatibilityActionpac damper control system
SealsPolyurethane and elastomeric rubber
Net Free Area (dm²)0.50 (Ø100) to 46.68 (Ø800)
Operating Temperature Range-20°C to 50°C
CertificationCE marking
HygieneTested by the Institute of Hygiene (Gelsenkirchen), VDI 6022 compliant — suitable for hospitals, clinics and pharmaceutical facilities
BearingsBrass
Mechanism positionOut of the airstream
Cross-Section (dm²)0.74 (Ø100) to 49.86 (Ø800)
Auto modeSpring-return motor, fail-safe closed
Maximum system pressure1000 Pa
LeakageClass 2 (closed blade), class C (casing) per EN 1751
Blade materialCalcium silicate
Mounting PositionVertical or horizontal blade axis (axis angle 0–360°)
ATEX versionII 2G Ex h IIC T6 Gb / II 2D Ex h IIIC T80°C Db (FIDI 21 ATEX D059), Schischek ExMax-5.10-BF actuator
FDC40 diameter range355 to 800 mm
Manual operationSpring-return mechanism and thermal release at 72°C
Maximum Air Velocity (actuators)Electric up to 12 m/s, EMS up to 10 m/s
FDC25 diameter range100 to 315 mm
TypeCircular single-blade fire damper, mechanical or automatic operation
Installation methodsStandard, Applique, MF1/MF2 and Remote — concrete/masonry and plasterboard, including installation away from the wall
Duct connectionCircular
Fire resistance classificationEIS (integrity, insulation, low smoke leakage)
Pressure DropΔp = ζ · v² · 0.6 — ζ: FDC25 Ø100 1.759 / Ø125 0.852 / Ø160 0.545 / Ø200 0.445 / Ø250 0.340 / Ø315 0.293 · FDC40 Ø355 0.428 / Ø400 0.389 / Ø450 0.344 / Ø500 0.325 / Ø560 0.312 / Ø630 0.232 / Ø710 0.206 / Ø800 0.179
Environmental DeclarationEPD (EN 15804+A2, ISO 14025)
Maximum air velocity12 m/s
Casing materialGalvanised sheet steel (also available in stainless steel or with electrostatic paint)
StandardsEN 15650, EN 1366-2, EN 13501-3, EN 1751
Casing Length380 mm
Activation Temperature72°C (standard) or 95°C (optional, with electric actuator)