Actionair
SMOKESHIELD
SMOKESHIELD is a multi-blade automatic fire damper, CE-marked with an ES classification, for square, rectangular or circular ducts. It restores fire compartmentation in the event of a fire, preventing the spread of fire and smoke. It closes either via the building's automatic fire detection system or via a local 72°C thermal release.
Download Technical Datasheet (PDF)Technical Specifications
CategoryPassive Fire Protection
BrandActionair
Test Cycles10,000 cycles
Flow DirectionIn both directions
CasingFully welded, 1.2 mm galvanised steel, with connection spigots
StandardsEN 15650, EN 1366-2, EN 13501-3
BladesAerodynamic interlocking, opposed blade, 75 mm, stainless steel
TypeMulti-blade automatic fire damper (SmokeShield PTC)
Duct tightnessClasses A and B per Eurovent Document 2/2; classes A, B and C per HVCA DW144
Installation methodsDWFX-F, DWFX-C, S&A (Sleeve & Angle with ablative batt), SPAN — concrete/masonry, plasterboard and composite wall systems
Size rangeWide range, with multiple banks possible for large-section ducts
Dimension Range100x100 mm to 1000x1000 mm (in 1 mm steps in width and height)
Fire resistance classificationES (integrity and low smoke leakage)
Maximum Air Velocity15 m/s
Blade sealsSynthetic, with steel end bearings and perimeter gasket
WeightWithout actuator (square); +4.4 kg for the actuator
Operating Time60 s drive to end position, 22 s spring return
WiringHalogen-free, low smoke and fume
ActuatorsM5 PTC 24V (10/2 W, 12.5 VA) · M6 PTC 230V (12/4 W, 14 VA) · a third type with volt-free contacts is also available
MotorsChoice of motors according to project requirements
Thermal Release (BAT)72°C or power failure, per BS 9999:2017
Acoustic DataPressure drop–velocity and sound power level charts with octave-band spectrum corrections (Series 501/601) for outlet and casing-radiated noise
Maximum System Pressure1500 Pa
Control compatibilityActionpac damper control system
Casing Thickness1.2 mm galvanised steel (BS EN 10346:2009)
Duct connectionSquare, rectangular or circular
ActuationBuilding automatic fire detection system or local thermal release at 72°C
CertificationCE marking