SMOKE COMMAND MCD
Actionair

SMOKE COMMAND MCD

SMOKE COMMAND MCD is a multi-blade smoke control damper, CE-marked with an ES classification, for automatic activation (AA) systems. It is intended for smoke extraction networks serving one or more fire compartments, as well as for combined smoke and environmental ventilation systems. Its HOT 400/30 classification allows it to cycle and adjust its position for 30 minutes at 400°C.

Download Technical Datasheet (PDF)
Technical Specifications
CategoryPassive Fire Protection
BrandActionair
Maximum System Pressure1000 Pa
CertificationCE marking
Size Range200x200 mm to 1000x1000 mm (in 1 mm steps in width and height)
StandardsEN 12101-8, EN 1366-10, EN 1366-2, EN 13501-4
Installation methodsDWFX-F (1.2 mm flange with 50 x 50 mm angles and 14 x 24 mm oval holes) in solid walls and plasterboard
Maximum Air Velocity15 m/s
Weight (square, without actuator)<200 mm: 3.4 kg · 400 mm: 6.5 kg · 600 mm: 10.8 kg · 800 mm: 16.2 kg · 1000 mm: 23.5 kg (+13 kg for actuator/thermal casing)
Running Time<60 seconds (open/close)
Blade Depth81.5 mm, double-skin, with high-temperature silicone
Thermal classHOT 400/30 — cycling and position control for 30 minutes at 400°C
Thermal CasingLightweight material with endothermic properties, extends actuator operation at high temperatures
Duct connectionSquare or rectangular, with spigots
Casing tightnessEurovent Document 2/2 classes A and B; HVCA DW144 classes A, B and C
Acoustic DataSound power level charts (Velocity × Pressure Drop) with octave-band spectrum corrections (63–8000 Hz) for outlet and casing-radiated noise
ActuatorsSCHM5-2P PTC: 24V AC/DC 50/60Hz (8W max) · SCHM6-2P PTC: 230V AC 50/60Hz (12W max) · IP54, 2 separate volt-free contacts
InstallationDWFX-F: 1.2 mm galvanised steel frame with 50x50 mm angles and 14x24 mm oval holes
ClassificationES (integrity and low smoke leakage)
MotorTwo-position (drive open / drive close), chosen according to the project requirements
TypeMulti-blade smoke control damper (AA - automatic activation)
Blade materialFerritic stainless steel 430 (1.4016) per BS EN 10088-2; optionally 316 (1.4401)
Operating Pressure Range-1000 to +500 Pa
Blade depth81.5 mm, aerodynamic double-skin with interlocking
Free area retainedOver 120 minutes at elevated temperatures
WiringHalogen-free low smoke (FP200 GOLD), 1 metre tail
SealsHigh-temperature silicone, synthetic gaskets, perimeter seal
Control compatibilityACTIONPAC damper control panels
Casing material1.2 mm galvanised sheet steel, double-skin, fully welded per BS EN 10142
Installation Wall ThicknessUp to 250 mm (PTC interface)