← Ventilation
RVP-C
Klimaoprema

RVP-C

Klimaoprema circular VAV damper, available in nominal diameters from Ø100 to Ø630 mm (body length 400-850 mm), for controlling airflow to the required set point with a flow range of 37 to 12,482 m³/h. It has a built-in differential pressure sensor and a high-accuracy PID controller, needs no maintenance, and can connect to Modbus, KNX, BACnet or MP-Bus. The casing is galvanised steel (optionally stainless) and the damper blade has EPDM sealing gaskets — it withstands differential pressure up to 1000 Pa and temperatures of 0-50°C, with tightness per EN 1751.

Download Catalogue (PDF)
Technical Specifications
CategoryVAV Dampers
BrandKlimaoprema
ATEX versionAvailable for explosive atmosphere areas
Declaration of IncorporationDoI 419/2020_03 (EN ISO 12100:2010)
Sealing Gasket MaterialEPDM
Communication ProtocolsMP-Bus, KNX, Modbus, BACnet, analogue 0-10V
Casing Length L (mm)400 (Ø100–Ø200), 500 (Ø250), 600 (Ø315–Ø400), 800 (Ø500), 850 (Ø630, with reinforcing ring)
Casing Outer Diameter ØDz (mm)198 / 223 / 258 / 298 / 348 / 413 / 453 / 498 / 598 / 728 (for Ø100–Ø630)
ActuatorsBelimo, Gruner, Siemens
Maximum Differential Pressure1000 Pa
StandardsEN 1751, VDI 6022, EN ISO 12100:2010
Nominal DiametersØ100 - Ø630 mm
Casing MaterialGalvanised steel (optionally stainless EN 1.4301/1.4404)
Control ModeAir supply or positive/negative pressure, per factory setting
Control Signal0(2)–10V, MP-Bus, Modbus RTU, BACnet MS/TP, KNX
Measuring Cross MaterialAluminium pipes
Casing TightnessClass C (EN 1751)
Mounting PositionAll orientations permitted (except units with pressure control accessories)
Body Length400 - 850 mm
InsulationOptional 50 mm mineral wool with double-skin casing to reduce casing noise
HygieneTested by the Institute of Hygiene (Gelsenkirchen), VDI 6022 compliant
SensorDynamic pressure 0–600 Pa, resolution ±1 Pa (built into the actuator, PID control)
Control Accuracy±5% for velocities >3 m/s, ±10% for 1.2–3 m/s, ±20% for <1.2 m/s
Operating Temperature Range0°C to 50°C
Closed Blade TightnessClass 3 (EN 1751)
Airflow Range37 - 12.482 m³/h
Maximum Air Velocity12 m/s