CategoryHeat Pumps & Fan Coils
BrandLG
Outdoor Unit Sound Pressure Level - Low Noise (dBA)38 (at 5 m)
PhaseThree-phase
Seasonal Heating Efficiency ηs (55°C water)137 %
Indoor UnitHN1600MC NK1
Cooling Output (kW)12.00 kW (A35/W18) / 12.00 kW (A35/W7)
Maximum Supply Water Temperature (°C)65 °C
Cooling EER4.75 (A35/W18) / 2.70 (A35/W7)
Heat Output (kW)12.00 kW (A7/W35) / 11.00 kW (A7/W55) / 11.00 kW (A2/W35)
Outdoor Unit Sound Pressure Level (dBA)39 (at 5 m)
Outdoor Unit Sound Power Level LW(A) (dB)61
Outdoor Temperature Operating Range (Heating)-25°C to 35°C
Indoor Unit Sound Power Level (dBA)44
Heating SCOP (55°C water)3.50
Electrical Characteristics3~/50Hz/380-415V
Seasonal Heating Efficiency ηs (35°C water)181 %
Indoor Unit Weight (kg)30.5
Recommended Circuit Breaker (A)16
Outdoor Unit Sound Power Level - Low Noise (dB)60
Heating COP5.04 (A7/W35) / 2.90 (A7/W55) / 3.65 (A2/W35)
Water Temperature Range (Domestic Hot Water)15°C to 80°C (above 55°C only with booster heater operation)
Heating Energy Class (35°C)A+++
Outdoor UnitHU123MRB U30
RefrigerantR32
Heating Energy Class (55°C)A++
Measurement ConditionsA: outdoor air temperature, W: leaving water temperature (LWT)
Refrigerant - DetailsR32, GWP 675, 2.1 kg
Water Pipe ConnectionsMale PT 1" (ISO 7-1), inlet/outlet
Supply Water Temperature Range (Cooling)5°C to 27°C (16°C to 27°C when no fan coil is used)
Outdoor Temperature Operating Range (Cooling)5°C to 48°C
Outdoor Unit Weight (kg)91.7
Outdoor Unit Dimensions (HxWxD mm)1380 x 950 x 330
Capacity (kW)12 kW
Indoor Unit Dimensions (HxWxD mm)850 x 490 x 315
Supply Water Temperature Range (Heating)15°C to 65°C
Heating SCOP (35°C water)4.60
Indoor Unit Sound Pressure Level (dBA)36 (at 1 m)