Fire Break
FIREBREAK FX500 PIPE COLLARS
FX500 collars are suitable for large-diameter pipes, especially plastic ones, where they pass through separating constructions. In a fire, the intumescent material inside the collar expands to fill the gap left by the burnt-out pipe, maintaining the integrity of the fire-rated partition. - Suitable for pipes from 200 mm to 400 mm - Available in stainless steel with easy closure - Easy installation with intumescent material only, no other tools needed. - Tested to EN 1366-3:2009, providing up to 4h fire resistance (EI 240) - Mainly tested in 100 mm thick walls; suitable for all materials and also for thicker walls. - Suitable for all types of plastic pipes, including ventilation.
Download Technical Datasheet (PDF)Technical Specifications
CategoryPassive Fire Protection
BrandFire Break
Tested penetrationsPVC-U pipes (EN 1329-1, EN 1452-2, EN 1453-1) with outer diameter 200–400 mm and plastic pipes with combustible nitrile rubber insulation
Fire ResistanceEI 240 (4 hours)
Service temperature rangeIndoor use, also suitable for temperatures below 0°C
CertificationCE (ETA 21/0209), UL International (UL-EU-00513-A1)
MaterialStainless steel, hinge with locking clip
Storage conditionsDry place, +5°C to +40°C
StandardEN 1366-3:2009
ClassificationEN 13501-2
Pipe diameter200mm – 400mm
Tested wall thickness100mm
Shelf lifeUnlimited (under the recommended conditions)
Collar height130mm
PropertiesNon-toxic, low smoke, mould-resistant, halogen-free, zero VOC, unaffected by humidity
FixingHinge and toggle latch, fixing lugs with 6 mm slot for M5 steel brackets
TypeLarge-diameter Pipe Collar FX500
StandardsEAD 350454-00-1104 (category Y2, use across the full ambient temperature range, including below 0°C)
Tested floorsRigid (concrete), minimum thickness 150 mm
Tested pipe end conditionsUncapped pipes (U/U), valid for all plastic pipe uses, including ventilation