Fire Break
FIREBREAK COMPOUND
This material is easy to use when mixed with water and creates a fire-rated smoke barrier in penetrations with many services of different shapes. - Materials tested to EN 1366-3:2009 & EN 1366-4:2006, achieving 4h fire resistance. - Tested with many different service materials: multiple cables, copper pipes, metal pipes etc. - Suitable for large openings of 1400 mm by any length in floors and 1500 mm by any width in wall openings - Easy to apply with any simple formwork and without a specialist technician. - Does not shrink. - Creates a gas / smoke and halogen barrier
Download Technical Datasheet (PDF)Technical Specifications
CategoryPassive Fire Protection
BrandFire Break
Service temperature range-5°C to +70°C (indoor use, high humidity)
Application Temperature Range+5°C to +40°C
Flexural strength (28 days)2,08 – 3,98 N/mm² (EN 993-6:1995)
Sound insulationup to 57 dB (Rw, EN ISO 10140-2)
Mixing ratioPowder/water approx. 2:1 by volume (thick or pourable consistency)
Compressive strength (28 days)8.51 – 14.51 N/mm² (powder/water ratio 2:1 to 3:1 by volume)
Density (after curing)1040 – 1200 kg/m³ (28 days, depending on the mixing ratio)
CertificationCE (ETA 21/0210), UL International (UL-EU-00643-A1-M1)
Maximum opening1400 mm (floor, any length) / 1500 mm (wall, any width)
Reaction to fireA1 (non-combustible, EN 13501-1)
StandardsEN 1366-3:2009, EN 1366-4:2006
Tested wall thickness100 mm (minimum, flexible partition walls)
VOC CategoryM1 (highest European class)
ColourWhite
Fire Resistance4 hours
ClassificationEN 13501-2, EAD 350454-00-1104 (category Y2)
Tested floorsRigid (concrete), minimum thickness 150 mm
TypeFire-stopping compound