LG
CHILLER ACHH045LBAB
Operating Voltage: 415 V/380 Hz Cooling/Heating Power (kW): 2.7/3.0 Cooling/Heating Capacity (kW): 148/164 Outdoor Unit Dimensions (mm), (L x H x W): 1528 x 2,293 x 2,154 Outdoor Unit Weight (kg): 970 Refrigerant Type / Charge (kg): R-410A / 4 x 7.0 Compressor (Type/Number): Scroll / 4 Outdoor Unit Noise Level (dB): 91
Download Technical Datasheet (PDF)Technical Specifications
CategoryHeat Pumps & Fan Coils
BrandLG
Cooling Power Input (kW)54.8 kW
Electrical Characteristics3 phases, 4 wires, 380~415 V
Residual Current Device (A)125
Compressor (Type/Number)Scroll / 4
Water Heat Exchanger TypePlate
Load Control Range20% to 100%
Water Heat Exchanger Pressure Drop (kPa)28.7
Airflow (m³/min)210 × 4 @ 1,000 rpm
Cooling SEER4.20
Supply Water Temperature Range (Heating)30°C to 55°C
Outdoor Unit Noise Level (dB)91
Fans (Type / Number)BLDC / 4
Refrigerant Type / Charge (kg)R-410A/ 4 x 7,0
Maximum Operating Pressure Refrigerant / Water (kg/cm²)42/10
Outdoor Unit Sound Power Level LW(A) (dB)91 (Cooling) / 92 (Heating)
Heating SCOP3.30
Outdoor Temperature Operating Range (Heating)-30°C to 35°C
Water Inlet/Outlet Pipe Diameter65A/65A
Heat Output (kW)164.0 kW (47 RT)
Outdoor Unit Weight (kg)970
Cooling EER2.7
Water Flow Minimum/Maximum (LPM)288/534
Outdoor Unit Sound Pressure Level (dBA)68
Heating COP3.00
Refrigerant - DetailsR410A, GWP 2087.5, 4 × 7.0 kg (58.45 t CO2eq)
Fan Motor Power (W)900 × 4
Outdoor Unit Dimensions (mm), (L x H x W)1528 x 2.293 x 2.154
Maximum Supply Water Temperature (°C)55 °C
Remote Control / CommunicationModbus
Supply Water Temperature Range (Cooling)4°C to 20°C
Heating Power Input (kW)54.7 kW
Compressor Oil (Type / Quantity)PVE / 1400 cc × 4
Outdoor Temperature Operating Range (Cooling)-15°C to 48°C
Rated Water Flow Cooling/Heating (LPM)411/470
Installation Area (m²/RT)0.078
Power Cable (mm² × cores)50 × 5
Cooling/Heating Capacity (kW)148/164
ProtectionsHigh/Low pressure, anti-freeze
Maximum Operating Current (A)96
Cooling Output (kW)148.0 kW (42.1 RT)
Operating Voltage415 V/380 Hz
Measurement ConditionsCooling: outdoor air 35°C, water 12/7°C. Heating: outdoor air 7°C, water 40/45°C.
Expansion ValveEEV (electronic)